Water use

How we estimate the water a campus uses each year from its electricity, its cooling and how efficient it is

View .md

The formula

482 to 701482 to 701482 to 701
Electricity, GWh/year
1.10 to 1.251.20 to 1.401.15 to 1.50
PUE
1.10 to 2.000.02 to 0.150.15 to 1.80
Litres per kWh of IT energy
Water each year110 to 340 Mgal1.8 to 23 Mgal13 to 290 Mgal

Why we divide by PUE

Cooling water scales with the energy the servers use, not with everything the campus draws. PUE is facility energy divided by IT energy, so facility electricity divided by PUE gives IT energy. Water per kWh is then applied to IT energy only.

PUE by cooling

Cooling PUE
Closed loop and chillers 1.20 to 1.40
Evaporative 1.10 to 1.25
Unknown 1.15 to 1.50
Operator fleet figure 1.10 to 1.40, unless the operator publishes its own

Water per kWh of IT energy

Cooling Litres per kWh
Closed loop, dry or direct to chip 0.02 to 0.15
Chillers seen from above 0.05 to 0.35
Evaporative 1.10 to 2.00
Evaporative, 4,500 or more free cooling hours 0.80 to 1.60
Evaporative, under 2,500 free cooling hours 1.40 to 2.40
Unknown 0.15 to 1.80
Unknown, 4,500 or more free cooling hours 0.10 to 1.40
Unknown, under 2,500 free cooling hours 0.20 to 2.20

When no cooling is named but the operator publishes a fleet-wide water figure, we use that operator’s range. Free cooling hours explains the climate adjustment.

Low and high end

The low end pairs low electricity with the highest PUE and the lowest water per kWh. The high end pairs high electricity with the lowest PUE and the highest water per kWh. Litres are converted at 0.264172 gallons per litre.

Published figures win

When a campus has a published water figure, the record shows it instead of the range. We prefer the operator’s own report, then a discharge permit, then a filing in gallons per day, which we multiply by 365.

InputThis campusWhere it comes from
Electricity each year482 to 701 GWh482 to 701 GWh482 to 701 GWhElectricity and power bill
PUE1.10 to 1.251.20 to 1.401.15 to 1.50The cooling type, or the operator's published figure
Water per kWh of IT energy1.10 to 2.00 L/kWh0.02 to 0.15 L/kWh0.15 to 1.80 L/kWhThe cooling type and climate
Water each year110 to 340 Mgal/year1.8 to 23 Mgal/year13 to 290 Mgal/year

When we show nothing

  • No electricity range and no published water figure
  • The site is flagged as not a data center