# Water use

How we estimate the water a campus uses each year from its electricity, its cooling and how efficient it is.

Source: https://docs.wattlas.io/methods/water-use/

## The formula

Electricity, GWh/year ÷ PUE × Litres per kWh of IT energy = Water each year

| Example | Electricity, GWh/year | PUE | Litres per kWh of IT energy | Water each year |
| --- | --- | --- | --- | --- |
| 100 MW, evaporative cooling | 482 to 701 | 1.10 to 1.25 | 1.10 to 2.00 | 110 to 340 Mgal |
| 100 MW, closed loop | 482 to 701 | 1.20 to 1.40 | 0.02 to 0.15 | 1.8 to 23 Mgal |
| 100 MW, cooling unknown | 482 to 701 | 1.15 to 1.50 | 0.15 to 1.80 | 13 to 290 Mgal |

## Why we divide by PUE

Cooling water scales with the energy the servers use, not with everything the campus draws. PUE is facility energy divided by IT energy, so facility electricity divided by PUE gives IT energy. Water per kWh is then applied to IT energy only.

## PUE by cooling

| Cooling | PUE |
| --- | --- |
| Closed loop and chillers | 1.20 to 1.40 |
| Evaporative | 1.10 to 1.25 |
| Unknown | 1.15 to 1.50 |
| Operator fleet figure | 1.10 to 1.40, unless the operator publishes its own |

## Water per kWh of IT energy

| Cooling | Litres per kWh |
| --- | --- |
| Closed loop, dry or direct to chip | 0.02 to 0.15 |
| Chillers seen from above | 0.05 to 0.35 |
| Evaporative | 1.10 to 2.00 |
| Evaporative, 4,500 or more free cooling hours | 0.80 to 1.60 |
| Evaporative, under 2,500 free cooling hours | 1.40 to 2.40 |
| Unknown | 0.15 to 1.80 |
| Unknown, 4,500 or more free cooling hours | 0.10 to 1.40 |
| Unknown, under 2,500 free cooling hours | 0.20 to 2.20 |

When no cooling is named but the operator publishes a fleet-wide water figure, we use that operator's range. [Free cooling hours](/methods/free-cooling-hours/) explains the climate adjustment.

## Low and high end

The low end pairs low electricity with the highest PUE and the lowest water per kWh. The high end pairs high electricity with the lowest PUE and the highest water per kWh. Litres are converted at 0.264172 gallons per litre.

## Published figures win

When a campus has a published water figure, the record shows it instead of the range. We prefer the operator's own report, then a discharge permit, then a filing in gallons per day, which we multiply by 365.

| Input | 100 MW, evaporative cooling | 100 MW, closed loop | 100 MW, cooling unknown | Where it comes from |
| --- | --- | --- | --- | --- |
| Electricity each year | 482 to 701 GWh | 482 to 701 GWh | 482 to 701 GWh | Electricity and power bill |
| PUE | 1.10 to 1.25 | 1.20 to 1.40 | 1.15 to 1.50 | The cooling type, or the operator's published figure |
| Water per kWh of IT energy | 1.10 to 2.00 L/kWh | 0.02 to 0.15 L/kWh | 0.15 to 1.80 L/kWh | The cooling type and climate |
| Water each year | 110 to 340 Mgal/year | 1.8 to 23 Mgal/year | 13 to 290 Mgal/year |  |

## When we show nothing

- No electricity range and no published water figure
- The site is flagged as not a data center

## What to watch for

Cooling type is known for only a small share of campuses, so most records use the widest range. A filing that names the cooling system narrows it a lot.