Free cooling hours

How many hours a year outside air at the site is cool enough to cool a data center without chillers

View .md

What we count

Hours per year with outside air below 15 °C at the site, from climate records for that point. A year has 8,760 hours.

Why it matters

Cooler air means fewer hours that need evaporative cooling or chillers. That moves both electricity and water use.

How it changes water estimates

For evaporative or unknown cooling, the water range shifts with the climate:

Free cooling hours Evaporative Unknown cooling
4,500 or more 0.80 to 1.60 L/kWh 0.10 to 1.40 L/kWh
2,500 to 4,499 1.10 to 2.00 L/kWh 0.15 to 1.80 L/kWh
Under 2,500 1.40 to 2.40 L/kWh 0.20 to 2.20 L/kWh

Litres per kWh of IT energy. See Water use.

When we show nothing

  • No climate record near the site