# Free cooling hours

How many hours a year outside air at the site is cool enough to cool a data center without chillers.

Source: https://docs.wattlas.io/methods/free-cooling-hours/

## What we count

Hours per year with outside air below 15 °C at the site, from climate records for that point. A year has 8,760 hours.

## Why it matters

Cooler air means fewer hours that need evaporative cooling or chillers. That moves both electricity and water use.

## How it changes water estimates

For evaporative or unknown cooling, the water range shifts with the climate:

| Free cooling hours | Evaporative | Unknown cooling |
| --- | --- | --- |
| 4,500 or more | 0.80 to 1.60 L/kWh | 0.10 to 1.40 L/kWh |
| 2,500 to 4,499 | 1.10 to 2.00 L/kWh | 0.15 to 1.80 L/kWh |
| Under 2,500 | 1.40 to 2.40 L/kWh | 0.20 to 2.20 L/kWh |

Litres per kWh of IT energy. See [Water use](/methods/water-use/).

## When we show nothing

- No climate record near the site

## What to watch for

Free cooling hours describe the climate, not the design. A campus can have many free cooling hours and still run chillers or evaporative cooling all year.